Eaton Freedom Series 3-Pole 1-Phase non-reversing non-combination full voltage starter has maximum voltage rating of 600-Volts AC and current rating of 45-Amps, 9 to 45-Amps over load relay. It has a coil voltage of 110-Volts AC at 50 Hz, 120-Volts AC at 60 Hz. The NEMA size 2 starter offers 1 NO-1 NC contact configuration. It withstands maximum load capacity of 10 hp at 200-Volts AC, 15 hp at 230-Volts AC, 25 hp at 460/575-Volts AC at 1-Phase. It has encapsulated dual voltage/frequency magnet coils permanently marked with voltage, frequency and part number. The screw type power terminals features captive, backed-out self-lifting pressure plates with +/-screws-reduced wiring time. The C440 solid-state electronic overload relay renders accurate, value driven and reliable protection including communication capabilities. Starter meets UL listed File E1491, cUL, CSA and CE standards.